Connection of the supply voltage
Fig. 19: Connection of the supply voltage
Table 12: Connector (X6)
Connector / Terminal
Pin
Assignment / Signal
X6 / L+
40
Supply v24 V DC
X6 / L+
41
Supply v24 V DC
X6 / M
42
Earth connection (0 V)
X6 / M
43
Earth connection (0 V)
X6 / functional earth
44
The functional earth (FE) is
connected to the Faston ter-
minal inside the device.
Ensure that no earth loops are
created and that FE and
Faston are connected to the
same earthing potential.
● In addition to connecting the supply voltage (L+/M) to X6, the supply voltage (UP/ZP) must
be connected to all connectors.
● ZP must be connected to all connectors (X1, X2, X3, X7, X8, X9).
● UP must be connected to all connectors (X7, X8, X9).
● L+/M and UP/ZP must always be supplied with voltage.
Connection for CS31 bus
Table 13: Connector (X5)
Connector / Terminal
Pin
Assignment / Signal
X5 / shield
37
Shield (functional earth)
X5 / B2
38
BUS2
X5 / B1
39
BUS1
Terminal "Shield" is internally connected to FE. The previous earthing meas-
ures, e.g. with clip at the switchgear cabinet, are still required.
“System data and CS31 bus system data” on page 4
AC31 Adapters
Replacement devices: CPU > Replacement device 07KT9x-AD