The replacement device does not provide a test button to measure functionality.
Table 55: Diagnosis information of the CS31 bus
Channel
Error code (COD-
ESYS)
Error code (CS31
bus bus)
Description
Device error:
0
43
1
Internal error
Channel error:
0 ... 7
45
9
Cut wire (is also indi-
cated if the current in
measuring range 4 ...
20 mA is less than 2
mA)
0 ... 7
49
10
Analog value is out of
measuring range
The error codes that are transferred by the replacement device via the CS31
bus bus are newly displayed in CODESYS. Each error code of the CS31 bus
(table column 3) produces the error code in CODESYS (table column 2). As a
result, it is possible to operate the replacement device with a new control
system (PLC/control unit), e.g. 07KT98-ARC-AD, as well as with an old control
system (PLC/central unit), e.g. 07KT98.
An exceedance of the measuring range is signaled even if nothing is connected
to an analog voltage input.
Table 56: Device LEDs
LED
Status
Color LED off
LED on
LED flashes
PWR
Voltage supply
Gree
n
No internal supply
voltage
Internal supply
voltage
-
CS31
bus
CS31 bus com-
munication
Gree
n
No CS31 bus com-
munication
CS31 bus bus
communication
Only diagnosis, no
data transfer. Trans-
mission is disturbed.
S-ERR
Error
Red
No error
Static error
(must be con-
firmed by the
control system)
No CS31 bus con-
nection or activity
I/O bus I/O bus commu-
nication
Gree
n
No I/O bus commu-
nication
I/O bus com-
munication
Error I/O bus com-
munication
The S-ERR LED remains on even if the error no longer occurs. The error must be confirmed by
the control system (PLC/central unit), e.g. by means of a function block
data and CS31 bus system data” on page 4