For further information, please refer to the existing documentation
System description Advant Controller 31.
Analog inputs
Data
Value
Number of channels per device
8
Connections
Connector X4 (terminals 3.0 … 3.3 and 7.0…
7.3)
Division of channels in groups
1 group with 8 channels (evenly distributed
among the modules DA501 and DA502 inter-
nally)
Common reference potential for analog inputs
(8 channels)
AGND1 (terminals 3.0 … 3.3 and 7.0…7.3)
Caution: internal reference to ZP via PTC
resistors
Electrical isolation
Max. permissible potential difference between
terminal ZP (minus the supply voltage) and
terminals AGND (minus the analog inputs and
outputs)
±
1 V
Caution: The internal reference is no longer M
but ZP.
Further information on page 25
Indication of the input signals
8 yellow LEDs to indicate the signal statuses
of the analog inputs (4 LEDs per DA501
module and DA502 module)
Configurability (optional per channel)
Chapter 1.4.1.3.1.2 “Connection of the
0 ... 10 V,
±
10 V (also with differential signal),
0 ... 20 mA, 4 ... 20 mA
Pt100 -50 ... +400 °C and -50 ... +70°C
Pt1000 -50…+400 °C (2-wire and 3-wire con-
figuration)
Digital input
Input resistance per channel:
-> Voltage input
> 100 kΩ
-> Current input
approx. 330 kΩ
-> Digital input
approx. 3.5 kΩ
Time constant of the input filter
Voltage: 100
µ
s, current: 100
µ
s
Conversion cycle
1 ms (for 4 inputs and 2 outputs)
1 s when measuring with resistance thermom-
eter Pt/Ni
The "Examples for the conversion cycle" from the existing documentation
07KT98 are no longer valid.
AC31 Adapters
Replacement devices: CPU > Replacement device 07KT9x-AD
2018/09/24
3ADR010122, 8, en_US
49