Data
Value
Averaging of measured values
not available
Resolution
8 bit
Unused voltage inputs
Can remain open or be short-circuited after GND or V+
to increase noise immunity
Overvoltage protection
Available
Overload range
±
30 V DC
Max. line length of analog lines, line
cross section > 0.14 mm²
100 m
*) Conversion cycle of MCU of I/O processing. The transmission via serial buses is slower.
For further information, please refer to the existing documentation
System description Advant Controller 31.
Table 100: Analog output
Data
Value
Number of channels
1
Connections
X3 / 6
Reference connections (GND)
X3 / 2, X3 / 7
Type of outputs
Voltage unipolar
Electrical isolation
not available
Nominal range
0 ... 10 V
Output load capability
max.
±
5 mA
Indication of the output signals
Replacement device: Not available
Existing device AX501: green LED per channel
Resolution
8 bit
Total errors (due to non-linearity,
offset, resolution and temperature)
Replacement device: max. 3 %
Existing device AX501: 0.6 %
±
1 digit
±
150 ppm/K
Update cycle
1.5 ms
Unused output
remains unconnected
Short-circuit-proof
Yes *)
External supply protection
Up to +30 V DC (no external supply protection available
for negative voltages!)
Max. line length of analog lines, line
cross section > 0.14 mm²
100 m
For further information, please refer to the existing documentation
System description Advant Controller 31.
AC31 Adapters
Replacement devices: I/O modules > Replacement unit DC501-CS31-AD
2018/09/24
3ADR010122, 8, en_US