Fig. 6: Direct earthing of CS31 bus master and CS31 slave
The shield connection of the CS31 bus master is internally connected to the
earth terminal.
Apply capacitative earthing if system parts are not connected to each other in terms of their cur-
rent carrying capacity. This prevents the flow of compensation currents through the cable
shields.
Fig. 7: Direct earthing of CS31 bus master and capacitative CS31 slave
On the CS31 slave, the shield connection is not connected internally and thus
not earthed. The shield connection can be used to connect the shields of two
cables.
VDE 0160 requires that the system's shield is earthed directly at least once.
No current car-
rying capacity
AC31 Adapters
System data and CS31 bus system data > CS31 bus system data