Digital inputs
Data
Value
Number of channels per device
16
Connections
Connector X2 (terminals X5.0…X5.7)
Connector X3 (terminals X6.0…X6.7)
Division of channels in groups
2 groups with 8 channels (not electrically iso-
lated!)
Voltage supply
UP (supplies module DA501 and 502)
Common reference potential:
-> for group 1 (8 channels)
ZP (terminals 5.0 ... 5.07)
-> for group 2 (8 channels)
ZP (terminals 6.0 ... 6.07)
Electrical isolation:
● Electrical isolation from group to group is
no longer available.
● Electrical isolation from DA501 and DA502
(reference ZP) to the rest of the device
(reference M) is available.
● On DA501 and DA502, all channels have
the same potential ZP. Voltage supply
UP/ZP.
● AGND1 and AGND2 of the analog chan-
nels are internally connected to ZP via
Configurability of the inputs
Input delay configurable (0.1 ms, 1 ms, 8 ms
and 32 ms). Default: 0.1 ms.
Channels for high-speed counters
Chapter 1.4.1.3.4.6 “Digital inputs/outputs”
Channels for high-speed counters are imple-
mented with the inputs/outputs (channels: 4.0
and 4.1).
Indication of the input signals
One yellow LED each per channel. The LED
corresponds functionally to the input signal.
Input signal voltage:
24 V DC
-> 0 signal
-3 V…+5 V
-> Undefined signal state
+5 V ... + 15 V
-> 1 signal
+15 V ... + 30 V
Input current per channel:
-> Input voltage = +24 V
Typ. 5.0 mA
-> Input voltage = + 5 V
> 1 mA
-> Input voltage = +13 V
> 2 mA
-> Input voltage = +30 V
< 8.0 mA
Max. cable length unshielded
600 m
Max. cable length shielded
1000 m
For further information, please refer to the existing documentation
System description Advant Controller 31.
AC31 Adapters
Replacement devices: CPU > Replacement device 07KT9x-AD
2018/09/24
3ADR010122, 8, en_US
46