Digital outputs
Data
Value
Number of channels per device
16 high-side switches
Connections
Connector X7 (terminals 1.0 ... 1.7)
Connector X8 (terminals 2.0 ... 2.7)
Division of channels in groups
2 groups with 8 channels (not electrically iso-
lated!)
Common voltage supply
UP (supplies module DA501 and 502)
Common reference potential ZP:
-> for group 1
ZP (terminals 1.0 ... 1.7)
-> for group 2
ZP (terminals 2.0 ... 2.7)
Electrical isolation
● Electrical isolation from group to group is
no longer available.
● Electrical isolation from DA501 and DA502
(reference ZP) to the rest of the device
(reference M).
● On DA501 and DA502, all channels have
the same potential ZP. Voltage supply
UP/ZP.
● AGND1 and AGND2 of the analog chan-
nels are internally connected to ZP via
Indication of the output signals
One yellow LED each per channel. The LED
corresponds functionally to the output signal.
Output current:
-> Rated value
500 mA at UP = 24 V
-> Residual current at 0 signal
< 0.5 mA
Demagnetization with inductive load
Internally via varistor
Switching frequency with inductive load
max. 0.5 Hz
Switching frequency with lamp load
max. 11 Hz at max. 5 W
Max. cable length
1000 m (shielded)
600 m (unshielded)
Short-circuit proof / overload proof
Yes
Protection against reversed voltage of process
supply voltage
Yes
Resistance to feedback against 24 V signals
Yes
Total load current (all DO channels, 1.0...1.7
max. 4A and 2.0…2.7)
max. 4 A
Total load current (all DC channels, 4.0..4.7
max. 8A and 8.0…8.7)
max. 8 A
Total load current (via UP) 16 DO channels
and 16 DC channels
max. 12 A (all UP terminals must be con-
nected)
For further information, please refer to the existing documentation
System description Advant Controller 31.
AC31 Adapters
Replacement devices: CPU > Replacement device 07KT9x-AD
2018/09/24
3ADR010122, 8, en_US
47