15. Common Items for Printer and Data Output
There are some similar functions and operations for the printer and the serial data
output (RS-232C, RS-422/485 and the current loop).
Data output / print output mode
Data number (not available for the current loop)
Interval data output or print out (not available for the current loop)
15.1. Data Output / Print Mode
Description of "Stream Mode" (For data output)
Function
f37
=
0
,
f40
=
0
Operation
The data is output at each sampling (when refreshing the display).
Use this mode to output data to an external display (The data may not be
output due to timing of the baud rate and internal sampling rate) or to print
data by pressing the
key on the printer.
The serial interface command can not be used at
f40
=
0
.
Description of "Manual Print"
Function
f37
=
1
,
f40
=
1
,
f60
=
1
Operation When
the
key is pressed or the external input is set to output or print,
the stable weight data is output or printed just once.
The serial interface command can be used at
f40
=
1
.
Description of "Auto Print Mode"
Function
f37
=
2
or
3
,
f40
=
2
or
3
,
f60
=
2
or
3
,
Operation
When the weight data enters the "inhibit region for output" and becomes
stable in the "permission region of output", the stable data is output or printed
just once. To use this mode, set
f02
to
1
to
10
, but not
0
.
The serial interface command can be used at
f40
=
2
or
3
.
For weighing (and removing) each object and printing the data.
In case of
f37
=
2
,
f40
=
2
,
f60
=
2
"Inhibit region for output" +5d. +5d < "permission region of output".
In case of
f37
=
3
,
f40
=
3
,
f60
=
3
-5d
"inhibit region for output" +5d.
"Permission region of output" < -5d, +5d < "permission region of output".
d: division (weighing interval) of the first range.
Description of "Accumulated Data Output/Print"
Function
f37
=
4
,
f40
=
4
,
f60
=
4
Operation When
accumulation
(manual or automatic) is performed, data is output or
printed automatically with the accumulated data.
The serial interface command can be used at
f40
=
4
.
15. Common Items for Printer and Data Output