Chapter 2: Installation
ZP2-A Series Installation Manual
35
Class B loop connection
Caution:
Class B loops do not comply with EN 54-13 requirements. Never install
more than 32 devices on a Class B loop.
Connect Class B loops as shown in Figure 16 below. Connection may be made
to either the A connectors (as shown) or to the B connectors, but not to both.
Class B loops are supervised for short circuit.
Figure 16: Class B loop connection