Chapter 3: Configuration and commissioning
ZP2-A Series Installation Manual
47
Restricted user levels
Restricted user levels are protected by password security. You are required to
enter the username and password assigned to you.
The control panel automatically exits from a restricted user level and reverts to
the public user level after a few minutes if no button is pressed. The automatic
timeout period depends on the active user level, as shown below.
Table 20: User level timeouts
User level
Automatic timeout period
Operator
2 minutes
Maintenance
10 minutes
Installer
10 minutes
To enter a password-protected level:
1. Press F4 (Main menu). The username and password prompt appears on the
LCD.
2. Select your username and enter your password by turning the jog dial
clockwise or anticlockwise. Press the jog dial to confirm each entry.
When a correct four-digit password has been entered, the LCD displays the Main
menu for your assigned user level.
Note:
The control panel can be configured to remember the last login details
entered. See “Secure access” on page 132 for more information.
To exit from a password-protected level:
1. Press F3 (Logout) from the Main menu.
Содержание ZP2-AF2-P
Страница 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Страница 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Страница 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Страница 153: ...Chapter 5 Technical specifications ZP2 A Series Installation Manual 147 Figure 29 Large cabinet dimensions and views...
Страница 154: ...Chapter 5 Technical specifications 148 ZP2 A Series Installation Manual Figure 30 Small cabinet dimensions and views...
Страница 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Страница 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Страница 176: ......