Chapter 1: Introduction
ZP2-A Series Installation Manual
11
Output group LED indications
The control panel can be configured to have several sounder, fire routing, or fire
protection output groups. Some groups may use the same indicators. When such
groups have the same status, that status is indicated. In the case of conflicting
status, the highest priority status is displayed.
Note:
For evacuation panels, indications for output groups associated with the
programmable buttons use the corresponding programmable button LEDs.
The following examples illustrate this operation.
There are three sounder output groups, the first in fault status, the second in
delayed status, and the third in activated status. The sounder indications display
the fault status of the first group, the delay status of the second group, and the
activated status of the third group.
There are two fire routing output groups, the first is in activated status and the
second is in acknowledged status. The fire routing indication displays the
acknowledged status but not the activation status (the acknowledgement status
takes priority).
For more information on output groups, see “Output groups” on page 113.
System Fault LED indication – maximum limit for event type reporting
A maximum limit of 512 events applies to each type of reported event (alarm,
zone alarm, fault, condition, etc.). This limit applies at panel level and per system
(including repeater panels).
The control panel indicates a System Fault when one or more event types
exceed the maximum limit (the fire panel continues to operate during the System
Fault indication).
A “System Overload” event is added to the Event log when one or more event
type exceeds the maximum limit.
Reset the control panel to clear the System Fault indication and reset the event
limit.
Содержание ZP2-AF2-P
Страница 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Страница 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Страница 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Страница 153: ...Chapter 5 Technical specifications ZP2 A Series Installation Manual 147 Figure 29 Large cabinet dimensions and views...
Страница 154: ...Chapter 5 Technical specifications 148 ZP2 A Series Installation Manual Figure 30 Small cabinet dimensions and views...
Страница 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Страница 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Страница 176: ......