Chapter 3: Configuration and commissioning
110
ZP2-A Series Installation Manual
Type
Description
MCP
Manual call point alarm.
This input type can be used for connecting to aspirating detector Fire2
outputs.
PREAL
Prealarm (unlatched).
This input type can be used for connecting to aspirating detector Action
outputs.
RST
Activation resets the panel remotely. To reset again, the input must be
deactivated, and then activated again.
FLT
External fault. Activation generates a latched fault event indicated as an
external fault.
DAY
Day mode. When this input is activated, the control panel switches to
day mode until the next scheduled night mode change (or until the
output is deactivated).
NIGHT
Night mode. When this input is activated, the control panel switches to
night mode until the next scheduled day mode change (or until the
output is deactivated).
FOS
Fault Warning Output Open Supervision. By using a 2010-FS-EOL end-
of-line device, the control panel can supervise the open circuit condition
of the Fault Warning output.
FRAK1
Fire routing acknowledgement (type 1). The input receives
acknowledgement from the remote monitoring equipment that the fire
routing signal was received correctly. If the acknowledgement is not
received within 100 seconds of fire routing activation, the control panel
reports a fire routing fault.
FRAK2
Fire routing acknowledgement (type 2). The input receives
acknowledgement from the remote monitoring equipment that the fire
routing signal was received correctly. If the acknowledgement is not
received within 240 seconds of fire routing activation, the control panel
reports a fire routing fault.
FPAK1
Fire protection acknowledgement (type 1). The input receives
acknowledgement from remote fire protection equipment. If the
acknowledgement is not received within 100 seconds of fire protection
activation, the control panel reports a fire protection fault.
FPAK2
Fire protection acknowledgement (type 2). The input receives
acknowledgement from remote fire protection equipment. If the
acknowledgement is not received within 240 seconds of fire protection
activation, the control panel reports a fire protection fault.
FP_FT
Fire protection fault. Used to indicate remote faults in fire protection
equipment.
FBFSD
Disable FBF sounder button (Akustische Signale). Used to interface to
remote FBF equipment to disable or enable sounders.
UKSB
British school class change. Activation activates sounders for 5 seconds
(not configurable) for school class change indication.
Содержание ZP2-AF2-P
Страница 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Страница 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Страница 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Страница 153: ...Chapter 5 Technical specifications ZP2 A Series Installation Manual 147 Figure 29 Large cabinet dimensions and views...
Страница 154: ...Chapter 5 Technical specifications 148 ZP2 A Series Installation Manual Figure 30 Small cabinet dimensions and views...
Страница 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Страница 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Страница 176: ......