Chapter 1: Introduction
ZP2-A Series Installation Manual
15
Conditions
A summary of system events logged as conditions is shown below.
Table 9: System events logged as conditions
Condition type
Description
Alert
A device is in alarm but the system is waiting for an
additional alarm event to confirm the zone alarm
Configuration device connected
A control panel configuration session is initiated via an
external device (PC, laptop, etc.)
Date and time not set
The system started but the date and time are not set
Change password
The default Operator, Maintenance, or Installer password
should be changed.
Disablements
A control panel feature or device is disabled
Event log full
The control panel event log is full
Extinguishing status [1]
Extinguishing is blocked, disabled, or has a fault
Extinguishing I/O device [1]
An extinguishing I/O device is active, being tested, is
disabled, or has a fault
Incompatible firmware version
An expansion board (for example, a loop board, a network
board, or DACT board) has an incompatible firmware
version. The control panel firmware version should be
updated.
Input activation
An input is activated (subject to configuration)
Loop device not configured
A loop device is detected that is not configured
Loop power
A loop power status is OFF
Loop recovery
A loop is in the recovery process (this may happen when a
short circuit fault is detected or after a reset if there was a
fault on the loop).
Maximum conventional zones
exceeded in a network
The number of conventional zones in a fire network
exceeds the maximum allowed
Maximum loops exceeded in a
network
The number of loops in a fire network exceeds the
maximum allowed
New node in the fire network
A control panel has been added to the fire network
Output group activation
An output group is activated
Prealarm
A device (and corresponding zone) is in prealarm
Sounder, fire routing, and fire
protection delays
A sounder, fire routing, or fire protection delay is enabled or
disabled
Tests
A control panel feature or device is being tested
[1] These condition types only apply if an extinguishing panel is included in the fire network.
Содержание ZP2-AF2-P
Страница 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Страница 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Страница 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Страница 153: ...Chapter 5 Technical specifications ZP2 A Series Installation Manual 147 Figure 29 Large cabinet dimensions and views...
Страница 154: ...Chapter 5 Technical specifications 148 ZP2 A Series Installation Manual Figure 30 Small cabinet dimensions and views...
Страница 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Страница 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Страница 176: ......