Chapter 3: Configuration and commissioning
98
ZP2-A Series Installation Manual
BMS Configuration
Select BMS Config to configure building management protocol settings (BACnet,
Modbus). By default neither protocol is enabled.
Table 45: BMS configuration options
Option
Description
Default value
Protoc
Configures the BMS protocol (NO, BACnet, or
Modbus)
NO
InitPan [1]
Configures the initial panel address when using
Modbus in Zonepoint mode
001
Mode [1]
Configures the Modbus mode (Zonepoint or Zone) Zonepoint
[1] Not applicable for BACnet.
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select BMS Config.
3. Configure all required settings.
Initpan is only required when using Modbus in Zonepoint mode.
Zonepoint mode implements Modbus services for 32 networked fire panels
with consecutive addresses (for example, 1 to 32 if the address of the first
panel is defined as 001 in InitPan).
Zone mode implements Modbus services for 128 networked fire panels
(InitPan is not required).
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Содержание ZP2-AF2-P
Страница 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Страница 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Страница 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Страница 153: ...Chapter 5 Technical specifications ZP2 A Series Installation Manual 147 Figure 29 Large cabinet dimensions and views...
Страница 154: ...Chapter 5 Technical specifications 148 ZP2 A Series Installation Manual Figure 30 Small cabinet dimensions and views...
Страница 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Страница 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Страница 176: ......