background image

JABLOTRON

ALARMS

a.s.

Pod

Skalkou

4567/33

46601

Jablonec

n.

Nisou

Czech

Republic

www

.jablotron.com

||

|

SD-283ST Wired combined smoke and heat detector 

SD-283ST  Wired combined smoke and heat detector 

1 / 2 

MLW55404 

 

The SD-283ST is used to detect fire hazards in the interior of 

residential or commercial buildings. The detector is also suitable for 
installing in caravan trailers or mobile homes. The product is not 
designed to be installed in industrial premises. 

 

The detector indicates fire hazard using the built-in LED indicator 

and acoustic signalling. The detector can also be powered from an 
external 12 V DC source or from the alarm system control panel 
and it provides ALARM and TMP outputs. When the detector is 
used with inserted batteries (3x 1.5 V AA), it can continue operating 
as a stand-alone detector when the external 12 V power supply is 
disconnected.  

The SD-283ST consists of two independent detectors – an optical 

smoke detector and a heat detector. The optical smoke detector 
works on the principle of scattered light. It is very sensitive to large 
dust particles which are present in dense smoke. It is less sensitive 
to smaller particles generated by the combustion of liquids such as 
alcohol. That is why the fire detector also contains a built-in heat 
detector which has a slower reaction but is much better at detecting fire 
which generates only a small amount of smoke.

 

Detector range and location 

The smoke detector must be installed so that any smoke easily 

drifts into the detector owing to natural thermal currents, e.g. on the 
ceiling. It is suitable for residential buildings but not suitable for free 
spaces, outdoor environments or interiors with extremely high 
ceilings (above 5 m) where fire by-products can disperse over a 
large area – the smoke would not reach the detector position. 

The detectors should be installed by a trained technician with a 

valid manufacturer’s certificate. 

Detectors should be installed in the building according to the 

project documentation. If such documentation is not available, their 
position should comply with the effective standards for fire alarm 
signalling systems. 

The detector must always be placed in the section leading to the 

exit of the building (escape route), see

 Fig. 1

. If the building has a 

floor area greater than 150 m

2

, installation of an additional detector 

in some other suitable place is required, see 

Fig.2

.  

 

 

  

1. kitchen, 

 

2. living room,  

3. – 6. bedrooms

  

 

y

 /

 

basic coverage

 

 

{

{

 /

 

recommended 

coverage

 

 

Fig 1 

 

Fig 2 

 

Fig 3

 

  
 

In multi-storey flats and family houses the detector should be 

installed above the stairs. It is recommended to place additional 
detectors in rooms where people sleep. See 

Fig 3

 

Installation on level ceilings 

Place the detector in the centre of the room if possible. The 

detector must not be recessed into the ceiling due to the 

possible existence of a cool air layer on the ceiling.

 

Never 

place the detector in the corner of the room (always keep at 
least 0.5 m distance from the corner - see Fig 4). There is an 
insufficient circulation of air in the corners.

 

 

Installation on sloping ceilings 

If the ceiling is not suitable for mounting on a level surface (e.g. a 

room under a roof ridge), the detector can be installed as in Fig. 5.  
 

 

Fig 1 

 

0,9 m

 

 

Fig 2 

centre of the room, best location 

 

 acceptable location 

Walls, partitions, barriers and lattice ceilings 

The SD-283ST detector must not be installed closer than 0.5 

m from any wall or partition. 

A narrow room with a width of less than 

1.2 m requires the detector(s) to be placed at a distance of at least one 
third of the room’s width away. In a case when a room is separated 
into sections with furniture, racks or semi partition walls which do 
not reach the ceiling, the space is considered to be fully separated 
if the gap between the top of these and the ceiling does not exceed 
0.3 m

.

 A free space of at least 0.5 m is required under and around the 

detector. Any irregularities of the ceiling (e.g. girders) exceeding 5 % of 
the ceiling height should be considered a wall and the above mentioned 
limitations should apply.  

Ventilation and air circulation 

The detectors must not be installed directly by ventilation or air 

conditioning vents.

 In the case of air being supplied through a 

perforated ceiling, each detector must be placed so that no 
perforation hole occurs within 0.6 m of the detector. 

Avoid installing the detector in the following locations:

 

x

  places with poor air circulation (niches, corners, apexes of A-

shaped roofs, etc.) 

x

  places exposed to dust, cigarette smoke or steam 

x

  places with over-intense air circulation (close to ventilators, 

heat sources, air conditioning outlets, etc.) 

x

  in kitchens and other cooking places (because steam, smoke or 

oily fumes can cause false alarms or reduce detector sensitivity). 

x

 beside fluorescent lights or energy-saving light bulbs 

(electrical interference can cause a false alarm) 

x

  in areas with lots of small insects 

 

Warning: 

Most false alarms are caused by improper detector 

location.

 

See CEN/TS 54-14 standard for detailed installation guidelines.

 

Installation 

When installing the detector, abide by the procedures 
recommended in the previous paragraphs. 

 

 

Fig 3: 1 – detector cover opening; 2 – detector cover closing; 3 – optical 

status signalling; 4 – arrow showing where to insert the detector; 5 – terminal; 

6 – configuration terminals; 7 – battery holders 

 

1. 

Open the detector cover

, by turning it anti-clockwise 

(1) 

 

2. 

Attach the base to the selected place using screws. 

 

Отзывы: