34 Operation and settings
4.3.8 The menu "OPERATING"
Contents: In menu "Operating", it is possible to change the national language, to allocate a password
and to carry out an additional parameter saving.
LASP
Selection of the national language
-Deutsch
-English
-Espanol
PW_E
If is is not possible to change the parameters when the drive is out
of action, first of all the set password has to be put in in this parameter.
No password has been allocated by the factory.
If a password is unknown, it is possible to ask the manufacturer. To do
this, please state the service number in
/ZA-INTERN/
SE_NR
(section INFO).
Figure 4.14 Menu structure
PW_N
Allocation or change of a password with four digits at the maximum ranging from 1 to 9999.
A password should only be put in after the commissioning has been completed.
Example: Allocation of password with number 12
1. Put in 12 in PW_N
2. Put in 12 a second time in PW_N
3. On the display appears blinking
4. After actuating a key, all parameters except PW_E are blocked.
5. In order to be again able to change parameters, the password (in this case 12)
has to be put in in parameter/PW_E.
PA_SI
The control device disposes of two parameter sets which can be changed-over by means of
one of the inputs "ZE1-3".
Besides the active working storage, each parameter set has a security storage.
The following parameter set operations are possible:
- OFF
Truncate function.
- W->S
Copy the current parameters from the working storage into the security storage.
- W<-S
Recopy already stored parameters from the security storage into the working
storage.
PARA 1->2 Copy parameter set 1 after parameter set 2.
RESET
With this parameter, it is possible to reset the control device to the initial delivery state. After
putting in number 99
and confirming an additional security inquiry, the factory setting is
loaded. After finishing this action (about 40 s), the indication appears that the control device is
to be switched off for a short time.
>Language
PW_E
OPERATING
**********************
LASP
PW_N
PA_SI
ENGLISH
. . . .
OFF
> Password input
. . . .
> New Password
> Parameter-saving
RESET
0
> Reset controller total
NEW PASSWORD
-----> 12
Содержание ZETADYN 1DV Series
Страница 2: ...http www bzxindaxin com http www gk world com 全球独家推出 全覆盖型省配线解决方案 ...
Страница 3: ...http www bzxindaxin com http www gk world com ...
Страница 4: ...http www bzxindaxin com http www gk world com ...
Страница 5: ...http www bzxindaxin com http www gk world com ...
Страница 6: ......
Страница 63: ......