A5 Error tracing plan
During commissioning, error messages can be caused by basic connection of triggering errors.
Therefore, please check the following four points.
Condition for a controlled operation:
Are the board of the controller board as well as the power stage connected to the same phases?
Is the correct encoder type adjusted in menu /INSTALLATION/GEBER ?
Conditions so that the control device is able to control start-up and stopping without jerk:
Is the spring-loaded safety brake switched on and off without delay by means of the relay "MB"?
Is the
main contactor "K0"
switched on and off without delay by means of the
relay "RB"
?
If the control does not evaluate the contact "RB":
Is the main contactor switched on at the latest when the driving command is fed?
Is the main contactor switched off time-delayed only when the brake comes in?
The error search plan is divided into the following sections:
A5.1
Error message at standstill
A5.2
Drive is not running.
Brake does not open and main contactor does not switch on
A5.3
Drive is not running.
Brake opens and main contactor switches on.
or accelerates and switches off.
A5.4
Drive switches off at deceleration.
A5.5
Drive switches to trouble when stopping.
A5.6
Checking the encoder.