Operation and settings 37
4.3.10 The menu "INTERFACES"
Contents: In menu "Interfaces", it is possible to change the factory functions of the programmable inputs
and outputs.
Function of the additional input "ZE3"
- V_ZE3
The input is used for selecting the speed V_ZE3.
The speed "V_ZE3" is put in in menu "TRAVELLING".
- 2.PARASET
This input switches to the second parameter set.
- Short travel
The input is activated for the "Short travel"- log.
Function of the special contact O SK 1
Contact K11-14 is closed if ...
- TEMP.MOT.
Motor temperature okay.
- QUIT. ZE3
Input I_ZE3 triggered.
- V=KONST.
Constant speed.
- V < V_G1
Limit value V_G1 is not exceeded.
Following this parameter, parameter V_G1 is faded in.
-
V<0.3m/s
Actual speed is smaller than 0.3 m/s.
- 1.1*V_NEN
Actual speed is smaller than 1.1*V_NEN.
Function of the special contact O SK 2
Contact K21-K24 is closed if...
- TEMP.MOT.
Motor temperature okay.
- QUIT. ZE3
Input I_ZE3 triggered.
- V=KONST.
Constant speed.
- V < V_G2
Limit value V_G2 is not
exceeded.
Following this parameter,
parameter V_G2 is faded in.
- V<0.3m/s
Actual speed is smaller than
0.3 m/s.
-
1.1*V_NEN
Actual speed is smaller than
1.1*V_NEN.
Function of the special contact O SK 3
Contact K34-K31 is closed if ...
- FB
Forced air cooling is to be
switched on.
-
TEMP.MOT
.
Motor temperature okay.
- QUIT. PA2
Second parameter set active.
- V<0.3m/s
Actual speed is smaller than
0.3 m/s.
- 1.1*V_NEN
Actual speed is smaller than
1.1*V_NEN.
Function of the output "Controller active -
RB"
- STANDARD
Relay is picked up during stop.
- I
NVERS
Relay is picked up during
running.
Selection of the trouble acknowledgement
Relay ST
- MANUAL
The relay trouble "ST" only
switches on again when the
controller release "RF" is
triggered again.
- AUTOMAT.
In case of excess temperature
of the motor or outage of a
mains phase, the relay "ST" is
automatically switched on
again if the trouble is
eliminated.
Other troubles have to be
acknowledged by means of
the controller release "RF" as
with "MANUAL".
INTERFACES
**************************
I_ZE3
O_SK1
V<0.3m/s
> Input ZE3
>
>
O_SK2
>
O_SK3
> Output RB
O_RB
> Error confirmation
QUIT
MANUELL
INVERS
TEMP.MOT
1.1V_NENN
V_ZE3
.
Output SK1
Output SK2
Output SK3
V_G1 0.200m/s
Speed level of O_SK1
V_G2 0.200m/s
Speed level of OSK2
Содержание ZETADYN 1DV Series
Страница 2: ...http www bzxindaxin com http www gk world com 全球独家推出 全覆盖型省配线解决方案 ...
Страница 3: ...http www bzxindaxin com http www gk world com ...
Страница 4: ...http www bzxindaxin com http www gk world com ...
Страница 5: ...http www bzxindaxin com http www gk world com ...
Страница 6: ......
Страница 63: ......