44 Commissioning
Elevator
••••
Elevator with a good installation
efficiency
,
i.e. when the cabin is empty and the brake is
manually opened, the cabin automatically
moves up.
T_VB
= 100 ms
M_VB = 0%
M_0
= 0%
Test runs EMPTY UP:
Increase M_VB setting until the cabin starts
moving smoothly.
Test run EMPTY DOWN:
Increase M_0 setting until motor only slightly
turns back when started. If the brake is not
already open, T_VB should be increased (in
steps of 50 ms).
••••
Elevator with a small installation
efficiency
, i.e. when the cabin is empty and
the brake is manually opened, the cabin only
moves when driving the handwheel.
T_VB
= 200 ms
M_VB = 25%
M_0
= 0%
Test run EMPTY DOWN:
In order to overcome an initial breakaway
torque, increase M_0 setting until the drive
starts without jerk.
Lifting gear
First of all check whether the drive moves
upward if RV1 is triggered. If not, exchange the
connection of RV1 and RV2 and change the
direction of the motor /INSTALLATION/MO_DR.
Running trials UP:
- Increase MO setting until the motor shaft no
longer turns back.
Running trials DOWN:
- Increase M_VB setting until the lifting gear
drives down without sagging.
Running gear
In case of running gears, the start-up process is
absolutely different from those of the other two
installation types.
When opening the brake, it is the driver winding
that is set under current. The torque which is
linearly driven increases until the initial
breakaway torque is surmounted. When the
motor starts moving, the installation switches to
the regulated operation.
T_VB
= 100 ms
M_VB = 30%
M_0
= 0%
M_0 is adjusted in a way that the drive runs
without jerk.The bigger M0 is, the faster the
change-over from the controlled to the regulated
operation.
5.5 Final of setting up
When the commissioning is finished, the current parameter setting has to be noted in the setting card
(Appendix A10 or in the short description).
The error list can be erased by means of the parameter /STATISTIC/STAT4.
When third persons (caretaker) have access too, the input should be protected by means of a password
(/OPERATING/PW_N see 4.3.8).
Содержание ZETADYN 1DV Series
Страница 2: ...http www bzxindaxin com http www gk world com 全球独家推出 全覆盖型省配线解决方案 ...
Страница 3: ...http www bzxindaxin com http www gk world com ...
Страница 4: ...http www bzxindaxin com http www gk world com ...
Страница 5: ...http www bzxindaxin com http www gk world com ...
Страница 6: ......
Страница 63: ......