Operating instructions type-lines CXE/AVC (E)
Date 0917
TBL02_13-GB 0917
Art.-Nr. 00153342-GB
Seite 5 / 63
3. General description
3.1 Scope of applications
Universal controller for clean room, refrigeration and air conditioning
Controlled 0-10 V „A1“ (Analog OUT 1) output e.g. for electronic speed controllers of fans
3.2 Technical data
Type
Part.No line voltage
internal device fuse
Weight
CXE/AVC 320006
1.05 kg
CXE/AVCE 320008
1~ 110 .. 277 V (-15 % bis +10 %), 50/60 Hz
T 400 mA (5x20 mm)
Art.Nr. 00153002
0.85 kg
CXE/AVC
320007 2~ 208 .. 415V (-15 % bis +10 %), 50/60 Hz T 400 mA (6,3 x 32mm)
Art.Nr. 00153840
1.05 kg
{
Input resistance for sensor or signal set for the rotational speed:
- for 0-10 V input: Ri
>
100 k
Ω
/ - bei Eingang 4-20 mA: Ri = 100
Ω
{
Voltage supply e.g. for s24 V ±20 %, I
max
120 mA
(
for connection to an external AXG terminal
minus ca. 50 mA
)
{
Output (0-) 10 V, I
max
10 mA (short-circuit-proof)
{
Heat dissipation approx. 6.5 W
{
Max. line fuse 10 A
{
The clock is buffered and has a 2-3 day reserve
{
Max. permissible ambient temperature 40° C
{
Min. permissible ambient temperature 0° C (
if mains voltage is not switched off up to -
20°C)
{
Permissible rel. humidity 85 % no condensation
{
Interference emission EN 61000-6-3
{
Interference immunity EN 61000-6-2
3.3 Versions Unicon
Type CXE/AVC Housing version IP54 for wall mounting
Type CXE/AVCE for panel mounting (IP54 mounted)