Operating instructions type-lines CXE/AVC (E)
Date 0917
TBL02_13-GB 0917
Art.-Nr. 00153342-GB
Seite 18 / 63
9.2.4 For mode
2.03
temperature controller with additional functions: Signal output 0-10 V
The 0-10 V output signal can, e.g., be used for triggering a shutter or heating.
The target value for this output is the target value (Setpoint) for the ventilation
±
offset setting.
Adjustment range
±
10 K relative to the active Setpoint.
Example for triggering a shutter servomotor:
At factory setting „0 K“ = synchronous operation.
The analog output is factory set to increasing activation during increasing temperature.
Reprogramming to „Heating function“, i.e., increasing modulation during decreasing
temperature is possible (
)
IO Setup).
Pband = separately adjustable range of control (P-band) for 0-10 V output
Min Analog Out = Minimal output voltage, setting range 0-100 % = 0-10 V
Max. Analog Out = Maximal output voltage, setting range 100-0 % = 10-0 V
Example for signal out 0-10 V
- Setpoint ventilation 25°C
- Offset -5 K
- Pband 10 K
↓
↑
↓
↑
↓
↑
Max. Analog Out
Min. Analog Out
100 %
50 %
Istwert / Actual
Min. = 0 %
Max. = 100 %
Min. = 35 %
Max. = 85 %
+/- Offset = 20 °C
Sollwert
Setpoint
10 K
Regelbereich
Pband
30 °C
A2 10 V