Operating instructions type-lines CXE/AVC (E)
Date 0917
TBL02_13-GB 0917
Art.-Nr. 00153342-GB
Seite 43 / 63
13. IO Setup
13.1 Analog Output A (Analog OUT 1)
13.1.1 Function analog output A (Analog OUT 1)
The analog outputs 0-10 V can be allocated with various functions.
Den analogen Ausgängen 0-10 V können unterschiedliche Funktionen zugeordnet werden.
Terminals 19 (A1) - 20 (GND) = Analog OUT 1 (I
max
10 mA) Pre-setting for speed controller input
Terminals 21 (A2) - 22 (GND) = Analog OUT 2 (I
max
10 mA)
The following functions can be assigned to the output
Function description
OFF no
Function
1 A
Constant v10 V (
factory setting
for A2, out of 2.03)
2 A
proportional modulation (
Factory setting A1
)
3 A
proportional input E1
4 A
proportional input E2
5 A
Group control
6 A
Control output 2 increasing modulation at actula value >Set (cooling)
(only mode
2.03
temperature controller with additional functions)
7 A
Control output 2 incresing modulation at actual value<Set (Heating)
(only mode
2.03
temperature controller with additional functions)
10 V
5 V
Analog out
modulation
0 50 100
0–100 %
Idealized principle diagram
Function 2 A proportional modulation
10 V
5 V
Input signal
Function 3 A / 4 A proportional input signal
0
1
2
3
4
5
6
7
8
9 10 0-10 V
10
9
8
7
6
5
4
3
2
1
0 10-0 V
0
2
4
6
8
10 12 14 16 18 20
0-20
mA
20 18 16 14 12 10
8
6
4
2
0 20-0 mA
4 5,6 7,2 8,8 10,4 12 13,6 15,2 16,818,4 20 4-20 mA
20 18,416,815,213,6 12 10,4 8,8 7,2 5,6 4 20-4 mA
For activ sensors 0-10 V Signal proportional
measuring range.
For passiv temperature sensors type TF..
(KTY10-6) proportional to -25 up to +80° C
(
1.303
Ω
up to 2.886
Ω
).
↓