Operating instructions type-lines CXE/AVC (E)
Date 0917
TBL02_13-GB 0917
Art.-Nr. 00153342-GB
Seite 28 / 63
-15° C
min. Temperature
+15° C
T-Start
50 %
Setpoint
1
P-min SA
Out door temp °C
9.4.2 Setting for operation modes
4.01
and
4.02
4.01
pressure control, setpoint in Pa
4.02
Pressure control for ventilation systems setpoint
depending on outdoor temperature Setpoint in Pa
(hPa, mbar) and temperature in °C.
Setpoint 1
Setting range:
in measuring range of sensor
Setpoint 2
Switch over 1/2 by external
contact
)
IO Setup
Control range „Pband“
small range = great amplification
and short control time
Big range = longer control times
(higher controller stability)
Minimal speed
0-100 %
Maximal speed
100% - Min.
OFF = automatic control
ON = manual speed setting
0 - 100 %
Manual speed setting
0 - 100 % if manual mode = ON
Additional menu item for mode
4.02
with outside-
temperature dependent target-setpoint
An outside temperature compensation can be activated
(sensor connection E2 to analog IN 2) when being operated
as a pressure regulation device. An optimal building climate,
e.g., can be achieved through this. Through this function, the
set and active Setpoint1/2 is automatically changed
proportional to the measured outside temperature (
)
Info:
“Setpoint control“).
Temperature range in which the
setpoint change continiously with
outside temperature
Setpoint reducing will start below this
outside temperature (start point)
Minimum pressure for very low
outside temperature
↓
↑
↓
↑
↓
P
↑