9. Programming
9.1 Speed controller
1.01
9.1.1 Basic setting
1.01
Factory setting Mode
1.01
Factory setting 0-10 V
Selection : 0-20 mA, 4-20 mA,
Bus
Inverting in IO Setup
Analog input 2 „E2“ factory set at
OFF
•
For operation with a second signal and switch over via
floating contact
(
)
IO Setup) set to function 1 E.
•
For operation with a second signal and automatic control
at the higher level. Set E2 Funktion to 4E.
9.1.2 Setting for operation
1.01
Manual speed setting
Set Internal 1
Set internal 2
Swich over1/2 by external contact
Minimal speed
0 - 100 %
Maximal speed
100% - Min.
ON = (factory setting)
speed setting by external signal
OFF =
Set internal 1
Diagram default signal and output voltage
Idealized principle diagram
↓
P
↑
ESC
↓
↑
↓
↑
↓
↑
↓
↑
↓
↑
Min.
100 %
50 %
0-100% = 0-10V
Signal
0 1 2 3 4 5 6 7 8 9 10
0-10
V
10
9
8
7
6
5
4
3
2
1
0 10-0 V
0 2 4 6 8 10 12 14 16 18 20
0-20
mA
20
18
16
14
12
10
8
6
4
2
0 20-0 mA
4
5,6 7,2 8,8 10,4 12 13,6 15,2 16,8 18,4 20 4-20 mA
20 18,4 16,8 15,2 13,6 12 10,4 8,8 7,2 5,6
4 20-4 mA
Min. 0 % Max. = 100 %
Min. = 35 % Max. = 85 %