Operating instructions type-lines CXE/AVC (E)
Date 0917
TBL02_13-GB 0917
Art.-Nr. 00153342-GB
Seite 21 / 63
9.2.7 Menu for temperature controller
2.01
..
2.05
Parameter
User Setting
PIN Input
.----
.----
.----
.----
.----
Language
GB
GB
GB
GB
GB
Reset
OFF
OFF
OFF
OFF
OFF
Mode
2.01
2.02
2.03
2.04
2.05
Unicon
1.06
1.06
1.06
1.06
1.06
Only Display
Value E1-E2
-2.4°C
Control value
26.1°C
E1 Actual
30°C
10°C
30.0°C
22.9°C
21.9°C
E2 Actual
.-----
.-----
.-----
26.1°C
24.3°C
Setpoint 1
20.0°C
5.0°C
20.0°C
20.0°C
0.0°C
Fanlevel
0,5
0,25
0,5
1
0
Msco.
OFF
OFF
OFF
OFF
OFF
Time
12:06
12:06
12:06
12:06
12:06
Date
18.07 05
18.07 05
18.07 05
18.07 05
18.07 05
Setpoint 1
20.0°C
5.0°C
20.0°C
20.0°C
0.0°C
Setpoint 2
.-----
.-----
.-----
.-----
.-----
Pband
5.0 K
20.0 K
5.0 K
5.0 K
5.0 K
Min. Speed
0%
0%
0%
0%
0%
Max. Speed
100%
100%
100%
100%
100%
Manual mode
OFF
OFF
OFF
OFF
OFF
Speed manual
100%
100%
100%
100%
100%
Offset AnalogOut
0.0K
Pband AnalogOut
2.0K
Min. AnalogOut
0%
Max. AnalogOut
100%
OffsetDigitalOut
-1.0K
Hyst.DigitalOut
1.0K
Alarm Minimum
0.0°C
Alarm Maximum
40.0°C
External Error
*
*
*
*
Sensor 1
*
*
*
*
Mode
2.01
2.02
2.03
2.04
2.05
E1 Analog IN
TF
TF
TF
TF
TF
E1 Min.
.----
.----
.----
.----
.----
2.01
Temperature control
E1 Max.
.----
.----
.----
.----
.----
E1 Decimals
.----
.----
.----
.----
.----
2.02
Temperature control depending on outdoor temperature
E1 unit
.----
.----
.----
.----
.----
E1 Offset
0.0K
0.0K
0.0K
0.0K
0.0K
2.03
Temperaturre control with additional functions:
E2 Function
OFF
OFF
OFF
4E
5E
Heating, shutter, temp. Monitoring
E2 Analog IN
.----
.----
.----
TF
TF
E2 Min.
.----
.----
.----
.----
.----
2.04
Temperature control with two Sensors
E2 Max.
.----
.----
.----
.----
.----
comparison with control to higher value
E2 Decimals
.----
.----
.----
.----
.----
average calculation of 2 measuring places
E2 unit
.----
.----
.----
.----
.----
E2 Offset
.----
.----
.----
0.0K
0.0K
2.05
Temperature control of 2 sensors
PIN Protection
OFF
OFF
OFF
OFF
OFF
regulation on difference temperature
Set protection
OFF
OFF
OFF
OFF
OFF
Save User Setup
OFF
OFF
OFF
OFF
OFF
Alarm Sensors
OFF
OFF
OFF
OFF
OFF
1E 0-10 V external Setpoint
Limit
.----
.----
OFF
.----
.----
2E external manual mode
Msco.
OFF
OFF
OFF
OFF
OFF
3E Sensor average to E1
ON Value Group2
.----
.----
.----
.----
.----
4E Sensor comparison to E1
nminm bei Gruppe2
.----
.----
.----
.----
.----
5E Sensor difference to E1
Val>Set = n+
ON
ON
ON
ON
ON
6E Sensor for setpoint lowering
Type of control
P
P
P
P
P
only for mode 4.02 and 5.02)
KP
50%
50%
50%
50%
50%
7 E measurement value for indication and display
KI
50%
50%
50%
50%
50%
KD
50%
50%
50%
50%
50%
TI
0%
0%
0%
0%
0%
S
e
tti
n
g
Ev
e
n
ts
INSTALLATION
B
a
se set
u
p
C
o
n
tro
lle
r S
e
tu
p
In
fo
factory setting
St
a
rt
E2 Funktion