9.6 Air velocity control
6.01
9.6.1 Basic setting
6.01
For mode
6.01
E1 factory setting to MAL1
selection sensor measuring range: MAL1,
MAL 10
Alternative selection signal: 0-10 V, 0-20 mA, 4-20 mA,
jumper accordingly inserted
.
The sensor measurement range must be entered in order
to display the actual value correctly. Example with a 0-10 V
sensor and 0-100° C measurement range
Initial value measuring range
Final value measuring range
Decimal places
display unit
9.6.2 Settings for operation modes
6.01
Setpoint 1
Setting range:
in measuring range of sensor
Setpoint 2
Switch over 1/2 by external contact
)
IO Setup
Control range „Pband“
small range = short control time
Big range = longer control times (higher
controller stability)
Minimal speed
0-100 %
Maximal speed
100% - Min.
OFF = automatic control
ON = manual speed setting0 - 100 %
Manual speed setting
0 - 100 % if manual mode = ON
Sensor calibration with calibrated
comparison device
Funktion analog Eingang 2
•
External setpoint = Function 1E
by external signal (0-10 V) instead of „Setpoint 1“
0-10 V ^ 0-100 % setting range
•
External manual operation = function 2E
via external signal (0-10V).
Switch over between settings on the device and external
manual operation via digital input
(
)
IO Setup).
•
Measurement value = function 7E
e.g. for limit indication, display in Info menu “E2 actual”.