Operating instructions type-lines CXE/AVC (E)
Date 0917
TBL02_13-GB 0917
Art.-Nr. 00153342-GB
Seite 47 / 63
13.2.3 Limit ON / OFF Function 3D
The value for Limit adjusted in the Controller Setup, is activated over a digital input („Digital IN 1“ = D1-D5 or Timer
function activates.
Limit value = max. possible modulation (e.g. speed reduction during night operation by time switch)
contact at digital inputs e.g. Digital IN 1 = D1-D1
Limit ON (limitation activ) at closed contat (factory setting)
D1 Inverting OFF
Limit ON (limitation activ) at opened contact
D1 Inverting ON
13.2.4 Switch over E1 / E2 Funktion 4D
Switch over between input signal 1 (at Analog IN 1 terminal E1) and input signal 2 (an Analog IN terminal E2)
contact at digital input e. g. Digital IN 1 = D1-D1
Signal from (E1) at opened contact
↔
Signal from “E2“ at closed contact
D1 Inverting OFF
Signal from (E1) at closed contact
↔
Signal from “E2“ at opened contact
D1 Inverting ON
Controller
0-100 %
D1 D1
0 1
0
1
0-80 %
A1
Output 0-10 V
A1
Output 0-10 V
Controller
0 -100 %
D1
D1
0
1
E1
GND
E2
GND
Signal 1
Signal 2
0
1
Signal 1
Signal 2