Operating instructions type-lines CXE/AVC (E)
Date 0917
TBL02_13-GB 0917
Art.-Nr. 00153342-GB
Seite 49 / 63
13.2.6 Intern / Extern Function 6D
♦
Switch over between Set Intern and Set Extern
(for mode speed controller
1.01
)
“Set external 1“ under settings must be programmed to OFF
contact at digital input e. g. Digital IN 1 = D1-D1
Set Intern 1 at opened contakt
↔
Set Extern at closed contact D1 Inverting OFF
Set Intern 1 at closed contakt
↔
Set Extern at opened contact D1 Inverting ON
♦
Switch over between aktiv setting at the unit and external Signal
(for mode controller higher
2.01
)
Contact at digital input e. g. Digital IN 1 = D1-D1
External Setpoint at 1E for E2 Funktion
External manual operation at 2E for E2 Function
Setting at the unit at opened contact
↔
Signal Extern at closed contact D1 Inverting OFF
Setting at the unit at closed contact
↔
Signal Extern at opened contact D1 Inverting ON
Signal 40%
Controller
78 % = Intern 1
D1
D1
0
1
0
1
40 % = Extern
E1
A1
Output 0-10 V
External Setpoint or
external hand mode
Signal 40 %
Controller
0-100 %
D1 D1
E2
0
1
Intern
Extern
INTERN = 0
EXTERN = 1
Sensor
0 1
E1
A1
Output 0-10 V