Operating instructions type-lines CXE/AVC (E)
Date 0917
TBL02_13-GB 0917
Art.-Nr. 00153342-GB
Seite 24 / 63
Modulation
100 %
50 %
actual
n-min = 0 %
n-max = 100 %
Setpoint 12 bar
Pband 5 bar
17 bar
↓
P
↑
ESC
Modulation
100 %
50 %
actual
n-min = 0 %
n-max = 100 %
Set point 35.0°C
Pband 7 K
42.0 °C
9.3.2 Setting for operation
3.01
..
3.04
3.01
Pressure control condensers, Setpoint in bar
3.02
Pressure control for condensers with input for refrigerant, Setpoint in °C
3.03
t w o sensors for dual circuit condenser, automatic regulation to the highest pressure (selection amplifier integrated)
operation display: „Control value“, Setpoint in bar
3.04
t w o sensors for dual circuit condenser with input for refrigerant automatic regulation to the highest pressure
(selection amplifier).
Setpoint in °C , also for different refrigerants suitably there comparison of the temperatures. Display during
operation: „Control value“
3.01
and
3.03
setting in bar
3.02
and
3.04
input for refrigerant setting in °C
Setpoint 1 (factory setting 12.0 bar)
Setting range:
in measuring range of sensor
Setpoint 1 (factory setting 35.0.°C
Setting range:
in measuring range of sensor
Setpoint 2
Switch over 1/2 by external contact
(
)
IO Setup
Setpoint
2
Switch over 1/2 by external contact
(
)
IO Setup
Control range „Pband“
small range = great amplification and
short control time
Big range = longer control times
(higher controller stability)
Control range „Pband“
small range = great amplification and
short control time
Big range = longer control times (higher
controller stability)
Minimal speed
0-100 %
Minimal speed
0-100 %
Maximal speed
100% - Min.
Maximal speed
100% - Min.
OFF = automatic control
ON = manual speed setting0 - 100
%
OFF = automatic control
ON = manual speed setting0 - 100
Manual speed setting
0 - 100 % if manual mode = ON
Manual speed setting
0 - 100 % if manual mode = ON
(Idealized prinziple diagram)
(Idealized prinziple diagram)
The factory default presets must be adapted to match the system conditions by a competent person
.