9.2.6 For mode
2.03
Relay output for temperature monitoring
If the set value for the minimum alarm is not reached or the set value for the maximum alarm is exceeded, a message is
generated via the alarm symbol in the display. In addition, „Lmt E1 min“ is displayed alternately with the actual value for
the minimum alarm and Lmt E1 max for the „Maximum alarm“. An external message follows via the factory-assigned K1
relay. (IO Setup : K1 function = 2K)
Example for display if temperature is falling below setting „Alarm Minimum“
Relay K1 disengages (if not inverted)
Example for display if temperature is exceeding setting „Alarm Maximum“
Relay K1 disengages (if not inverted)
↓
↑