Operating instructions type-lines CXE/AVC (E)
Date 0917
TBL02_13-GB 0917
Art.-Nr. 00153342-GB
Seite 48 / 63
13.2.5 Set Intern 1 / Set Intern 2 or. Setpoint 1/2 Function 5D
♦
Switch over between Set Intern 1 and Set Intern 2
(for speed controller
1.01
)
Operation with “Internal default 2“ is signalized by the moon symbol for reduced operation.
“Set external 1“ under settings must be programmed to OFF.
contact at digital input e. g. Digital IN 1 = D1-D1
Set Intern 1 at opened contact
↔
Set Intern 2 at closed
contact
D1
Inverting
OFF
Set Intern 1 at closed contact
↔
Set Intern 2 at closed
contact
D1
Inverting
ON
♦
Switch over between Setpoint 1 and Setpoint 2
(for modes as controller higher
2.01
)
operation with „Setpoint 2“ is signalized by the moon symbol for reduced operation.
contact at digital input e. g. Digital IN 1 = D1-D1
Setpoint 1 = 18° C at opened contact
↔
Setpoint 2 = 25° C at closed contact D1 Inverting OFF
Setpoint 1 = 18° C at closed contact
↔
Setpoint 2 = 25° C at opened contact D1 Inverting ON
A1
Output 0-10 V
Controller
D1 D1
0 1
0-100 %
Sensor
Controller
3~ 400 V
78 % = Intern 1
D1
D1
0
1
0
1
40 % = Intern 2
A1
Output 0-10 V