Operating instructions type-lines CXE/AVC (E)
Date 0917
TBL02_13-GB 0917
Art.-Nr. 00153342-GB
Seite 27 / 63
9.4 Pressure control for ventilation systems
4.01
..
4.03
9.4.1 Basic setting
4.01
..
4.03
Analog In E1 factory setting to DSG200
Selection sensor measuring range: DSG 50, *DSG100
DSG200, *DSG300 DSG500, DSG1000, DSG2000,
DSG4000, DSG6000
(* no Ziehl-Abegg standard type)
For sensors with 0-20 mA, 4-20 mA signal put Jumper
accordingly and select measuring range DSG50 ..
DSG6000.
For not preprogrammed measuring range the sensor
measurement range must be entered in order to display
the actual value correctly.
Example with a 0-10 V sensor and 0-400 Pa
measurement range (proportional output signal)
Initial value measuring range
Final value measuring range
Decimal places
display unit
Sensor calibration with
calibrated comparison device
Function Analog Input 2
•
External setpoint = Function 1E
by external signal (0-10 V) instead of
„Setpoint 1“
0-10 V ^ sensor measuring range
•
External manual operation via external signal (0-10V) =
function 2E
Switch over between settings on the device and external
manual operation via digital input
(
)
IO Setup).
•
Measurement value = function 7E
e.g. for limit indication, display in Info menu “E2 actual”
•
Modes with two sensors
The function is automatically jointly programmed in
operating modes using 2 sensors. The second analog
input is thus allocated and additional function allocations
are not possible.
4.02
E2 Function at 6E preprogrammed = sensor for setpoint
lowering.
preprogrammed sensor type TF..
↓
↑
↓
P
↑
ESC