4.4
Installation location for agriculture
When using for animal keeping, do not install the device directly in the stable but in a separate room
with a lower pollutant load. This helps to avoid damages caused by pollutant gases (e.g. ammonia
fumes, hydrogen sulphide fumes).
4.5
Temperature in
fl
uences during commissioning
Avoid condensation in the controller and functional faults attributable to condensation by storing the
controller at room temperature!
5
Electrical installation
5.1
Safety precautions
Danger due to electric current
•
Work on electric components may only be carried out by trained electricians or by persons
instructed in electricity under the supervision of an electrician in accordance with electrical
engineering regulations.
•
The 5 electrical safety rules must be observed!
•
It is forbidden to carry out work on electrically live parts. Even after disconnection, the dc-link is still
live. Always wait at least 3 minutes.
•
Cover neighbouring electrical equipment during installation work.
•
Other measures may be necessary to achieve safe electrical isolation.
•
A second person must always be present when working on energized parts or lines who
disconnects in case of emergency.
•
Electrical equipment must be checked regularly: Loose connections are to be re-tightened and
damaged cables must be replaced immediately.
•
Always keep switch cabinets and all electrical supply facilities locked. Access is only allowed for
authorized persons using a key or special tool.
•
Operating the device with the housing cover removed is prohibited because energized, exposed
parts are present inside the device. Disregarding this regulation can lead to severe personal injury.
•
For metal cable inlets the necessary protective earth connection to the bottom of the housing is
made by screws. The device may only be started up when these screws are
fi
tted properly.
•
The required protective earth connection is established using screws between the housing parts in
metal terminal space covers and housing casings. Commissioning is only permissible after these
screws have been properly attached!
•
Metal screwed-connections are not permitted in plastic housing parts because there is no potential
equalization.
•
The device owner is responsible for the EMC of the entire plant according to the locally applicable
standards.
•
Never clean electrical equipment with water or similar liquids.
Information
The respective connections are represented in the enclosure of this Operating Instructions (see
connection diagram)!
5.2
EMC-compatible installation
5.2.1
Motor cable
The applicable standard for interference emissions is EN IEC 61000-6-3. Compliance with this stand-
ard is achieved through the use of an unscreened motor feed cable.
5.2.2
Control cables
Pay attention to su
ffi
cient distance from powerlines and motor wires to prevent interferences. The
control cable may not be longer than 30 m. Screened control cables must be used when the cable
length is longer than 20 m. When using a shielded cable connect the shielding to one side only, i.e.
only to the control unit with the protective ground (keep cable short and with as little inductance as
possible!).
Operating Instructions
Fcontrol
–
model series FTET4/6/10AHMQ
Electrical installation
L-BAL-E094-GB 2022/47 Index 007
Part.-No.
9/46