9.4.1.2
Example for two-position control independent of the ventilation nominal value
•
In installation menu
“
Mode 1
”
= Two-position controller, heating input:
“
1
”
=
“
E2
”
•
Current heating value from sensor on input
“
E2
”
Heating Setpoint
Heating Setpoint
Heater switch-on adjustable as a separate setpoint (i.e., in
°
C)
Setting range: -10.0...+40.0
°
C
Factory setting: -2.0
°
C
Heat. hysteresis
Heat. hysteresis
Positive hysteresis value =
Heating function
Relay
|
ON
|
as long as the temperature around the hysteresis is above the switch-on
point.
Negative hysteresis value =
Cooling function
Relay
|
OFF
|
if the temperature around the hysteresis is below the switch-on point.
Setting range: -10...+10 K
Factory setting: 0.5 K
Attention!
When setting a negative hysteresis, the function is inverted, i.e.,
“
Cooling function
”
Positive hysteresis value =
Heating function
0
1
12.08.2008
v_heiz_pos_hys_abs.vsd
H
S
A [°C]
H
Hysteresis
S
Setpoint
A
Compartment temperature
0
Heating OFF
1
Heating ON
Negative hysteresis value =
Cooling function
0
1
12.08.2008
v_heiz_neg_hys_abs.vsd
H
S
A [°C]
H
Hysteresis
S
Setpoint
A
Compartment temperature
0
Heating OFF
1
Heating ON
9.4.2
Controlling the heating via the 0...10 V signal (linear)
Example for controlling the heating via the 0 - 10 V signal (mode 2 = proportional controller)
The heating, activated through the 0 - 10 V signal, is indicated in the display with the
fi
re symbol as
soon as the activation exceeds
“
0 %
”
.
The
“
K2
”
heating relay is connected in parallel in order to activate, for example, a gas valve.
Heating o
ff
set
Heating o
ff
set
Heating related to the ventilation setpoint (i.e. o
ff
set adjustment in Kelvin)
in heating installation menu input:
“
0
”
=
“
E1
”
Current heating value = Current ventilation value (i.e., temperature from sensor on
input
“
E1
”
)
Setting range: -10.0...+10.0 K
Factory setting: -2.0 K
or
Heating Setpoint
Heating Setpoint
Heating is adjustable as a separate setpoint (i.e. in
°
C)
in heating installation menu input: 1 =
“
E2
”
Current heating value from sensor on input E2
Setting range: -10.0...+40.0
°
C
Factory setting: -2.0
°
C
Operating Instructions
Fcontrol
–
model series FTET4/6/10AHMQ
Settings for operation
L-BAL-E094-GB 2022/47 Index 007
Part.-No.
34/46