9.2.2
For throttle shutter control
The shutter function is used to control one throttle shutter in the chimney above or below the fan.
Shutter o
ff
set
Shutter o
ff
set
Setpoint for throttle shutter (on 0 - 10 V output
“
Shutter
”
) = setpoint
±
o
ff
set
Setting range: -10.0...+10.0 K
Factory setting: -1.0 K
If the output is to operate independently on another temperature source (
Installation
- Shutter), an independent
“
shutter setpoint
”
in
°
C must be entered alternatively.
Setting range: -10.0...+40.0 K
Factory setting: -10.0 K
Shutter Pband
Shutter Pband
Control range
“
Pband
”
for shutter
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range: 0.1..10.0 K
Factory setting: 2.5 K
Shutter Min.
Shutter Minimal
Setting range: 0...100 %
Factory setting: 0 %
Shutter max.
Shutter Maximal
Setting range: 100...0 %
Factory setting: 100 %
Example: Setpoint ventilation 25.0
°
C, O
ff
set -5.0 K, Pband 10.0 K
K
max.
19.08.2008
v_klappe_pte.vsd
S / V
A [°C]
K [%]
K
min.
R
K
Flap opening in % (without output curve)
K max.
Shutter Maximal
Kmin.
Shutter Minimal
S / V Ventilation Se/- Shutter o
ff
set
R
Shutter Pband
A
Compartment temperature
The throttle shutter
’
s setpoint results from the se/-
“
shutter o
ff
set
”
.
In the sample values shown, shutter control starts at 19.0
°
C; at 21.5
°
C it is 100 % open.
The throttle shutter can be coupled to the ventilation level control if necessary (
Installation
–
Shutter).
Information
The control output
“
Shutter
”
(0 - 10 V) is inverted at the factory, i.e. 10 V
…
0 V (10 V = shutter closed,
0 V = shutter completely open). This setting causes the shutter to open in the case of a line break to
the servo motor or failure of the control output (controller side) and avoids impairing the ventilation.
Operating Instructions
Fcontrol
–
model series FTET4/6/10AHMQ
Settings for operation
L-BAL-E094-GB 2022/47 Index 007