9.4.1
Heating control by relay (two-point mode)
9.4.1.1
Example for two-position control independent of the ventilation nominal value (factory setting)
•
In installation menu
“
Mode 1
”
= Two-position controller, heating input =
“
0
”
=
“
E1
”
•
Current heating value = Current ventilation value (i.e., temperature from sensor on input
“
E1
”
)
Heating o
ff
set
Heating o
ff
set
Heating switch-on point related to ventilation setpoint (i.e. o
ff
set setting in Kelvin)
Setting range: -10...+10 K
Factory setting: -2.0 K
Heat. hysteresis
Heat. hysteresis
Positive hysteresis value =
Heating function
Relay
|
ON
|
as long as the temperature around the hysteresis is above the switch-on
point.
Negative hysteresis value =
Cooling function
Relay
|
OFF
|
if the temperature around the hysteresis is below the switch-on point.
Setting range: -10...+10 K
Factory setting: 0.5 K
Attention!
When setting a negative hysteresis, the function is inverted, i.e.,
“
Cooling function
”
Positive hysteresis value =
Heating function
0
1
08.08.2008
v_heiz_pos_hys_rel.vsd
H
S + V
A [°C]
H
Hysteresis
S+V
Se o
ff
set
A
Compartment temperature
0
Heating OFF
1
Heating ON
Negative hysteresis value =
Cooling function
0
1
08.08.2008
v_heiz_neg_hys_rel.vsd
H
S + V
A [°C]
H
Hysteresis
S+V
Se o
ff
set
A
Compartment temperature
0
Heating OFF
1
Heating ON
Operating Instructions
Fcontrol
–
model series FTET4/6/10AHMQ
Settings for operation
L-BAL-E094-GB 2022/47 Index 007
Part.-No.
33/46