Operating Instruction
Econtrol
–
model series EXDM
Enclosure
L-BAL-E008-GB 0945 Index 005
Part.-No. 00156742-GB
80/85
Type
(Part-No.)
Rated cur-
rent*
Output
{1}
[A]
Rated current
(
I
fundamen-
tal component
@ 50 Hz)
Input
{1}
[A]
Max. line fuse
{2}
[A]
Max. heat
dissipation
approx.
{1}
[W]
Noise ap-
prox.
{3}
[dB]
Weight
[kg]
Housing pro-
tection
IP
EXDM10AE
(306576)
x
10
10 (/)
16
200
54.6
7.6
20
EXDM14
(306600)
x
14
14 (/)
16
300
/
12.2
54
EXDM14
(306616)
14
14 (12.3)
16
240
/
7.5
54
EXDM14A
(306601)
x
14
14 (/)
16
300
/
12.2
54
EXDM14A
(306615)
14
14 (12.3)
16
240
/
7.7
54
EXDM14E
(306602)
x
14
14 (/)
16
300
/
12.2
20
EXDM14AE
(306603)
x
14
14 (/)
16
300
/
12.2
20
x
= device will be replaced by a new vesion
(/) = no indication
* The name plate data for rated current refer to a maximum ambient temperature of 40
°
C. For higher temperatures note
details for operation with higher ambient temperature, these are available on request of the manufacturer.
{1} for mains voltage 400 V / 50 Hz, values for different speci
cations on request
{2} Max. supply side line fuse according to DIN EN 60204-1 classi
cation VDE0113 chapter 1
{3} Sound power level A-weighted by internal fan, (/ no fan), (- no indication)
Line voltage*
3 ~ 208...480 V (-15 up to +10 %), 50/60 Hz
Power factor
> 0.9
Clock frequency
16 kHz
Input resistance for sensor or signal set for
the rotational speed
for 0 - 10 V input: R
i
>100 k
Ω
for 4 - 20 mA input: R
i
= 100
Ω
Voltage supply e.g. for sensors
+24 V
±
20 %, I
max
120 mA (for connection to an external AXGterminal minus
approx. 50 mA)
Output (0 - 10 V)
I
max
10 mA (short-circuit-proof)
max. contact rating of the internal relay
2 A / 250 VAC
Max. permissible ambient temperature
40
°
C (up to 55
°
C with derating)
Min. permissible ambient temperature
0
°
C (if mains voltage is not switched off up to -20
°
C)
Max. permissible installation height
above 0...4000 m amsl. Above 1000 m amsl the rated current is to be reduced by 5
% / 1000 m
Permissible rel. humidity
85 % no condensation
Electromagnetic compatibility for the
standard voltage 230 / 400 V according to
DIN IEC 60038
Interference emission EN 61000-6-3 (domestic household applications)