E1 Modus
E1 Modus
|
0
|
= E1 min. / E1 max. without function (factory setting)
|
1
|
= Offset / turn
|
2
|
= signal range
|
3
|
= Hysteresis setting On / Off
E1 Min.
E1 Min.
Setting range: 0 - 100 %
Factory setting: 0 %
E1 max.
E1 max.
Setting range: 0 - 100 %
Factory setting: 100 %
E2 Mode
E2 Mode
|
0
|
= E2 min. / E2 max. without function (factory setting)
|
1
|
= Offset / turn
|
2
|
= signal range
E1 Min.
E2 min.
Setting range: 0 - 100 %
Factory setting: 0 %
E1 max.
E2 max.
Setting range: 0 - 100 %
Factory setting: 100 %
Example for Mode
“
1.01
”
with speed setting signal 0 - 10 V
n [%]
Si E
0
1
2
3
4
5
6
7
8
9
10
0 – 10 V
12.10.2009
v_e1_modus_1_prz.vsd
1
Modus 1
E1 min. = 0 %, E1 max. = 100 %
100
2
E1 min. = 25 %, E1 max. = 100 %
80
60
40
20
3
E1 min. = 20 %, E1 max. = 80 %
E1 min. = 0 %, E1 max. = 80 %
4
Modus 1
Example:
“
E1 min.
”
= 20 %
The controller begins only at approx. 20%
higher signal with minimal speed.
Example:
“
E1 max.
”
= 80 %
Speed rises linear to 100% speed with 80%
setting signal.
Si E
0
1
2
3
4
5
6
7
8
9
10
0 – 10 V
12.10.2009
v_e1_modus_2_prz.vsd
1
Modus 2
E1 min. = 0 %, E1 max. = 100 %
100
2
E1 min. = 40 %, E1 max. = 100 %
80
60
40
20
3
E1 min. = 30 %, E1 max. = 90 %
E1 min. = 0 %, E1 max. = 80 %
4
n [%]
Modus 2
Example:
“
E1 min.
”
= 30 %
Only with approx. 30 % setting signal the
controller begins with approx. 30% speed.
Example:
“
E1 max.
”
= 80 %
Over 80 % setting signal the speed is
switched to 100 %.
Operating Instruction
Econtrol
–
model series EXDM
Programming
L-BAL-E008-GB 0945 Index 005
Part.-No. 00156742-GB
60/85