9.3.4Menu pressure controller refrigeration
3.01
...
3.04
Parameter
Factory setting
User
Setting
Start
Motor
OFF
OFF
OFF
OFF
(Menu dependent on device type available)
PIN input
- - - - -
- - - - -
- - - - -
- - - - -
Language
GB
GB
GB
GB
Reset
OFF
OFF
OFF
OFF
Mode
3.01
3.02
3.03
3.04
Econtrol
1.14
1.14
1.14
1.14
SN:
xxx
xxx
xxx
xxx
Info
Control value
12.0 bar
22.6
°
C
E1 Actual
10.0 bar
19.5
°
C
9.5
°
C
19.4
°
C
E2 Actual
- - - -
- - - -
12.0 bar
22.5
°
C
3.01
Pressure control condensers, Set-
point in bar
Setpoint1
12.0 bar
35.0
°
C
12.0 bar
35.0
°
C
Speed
0 rpm
0 rpm
0 rpm
0 rpm
Motor current
0.0 A
0.0 A
0.0 A
0.0 A
Minimum speed
cut off
OFF
OFF
OFF
OFF
3.02
Pressure control for condensers with
input for refrigerant, Setpoint in
°
C
Setting
Setpoint1
12.0 bar
35.0
°
C
12.0 bar
35.0
°
C
Setpoint2
- - - -
- - - -
- - - -
- - - -
Pband
5.0 K
7.0 K
5.0 bar
7.0 K
3.03
2 sensors for dual circuit condensers
regulation to the highest actual value
(selection ampli
er integrated) Set-
point in bar.
Min. Speed
0 rpm
0 rpm
0 rpm
0 rpm
Max. Speed
200 rpm
200 rpm
200 rpm
200 rpm
Manual mode
OFF
OFF
OFF
OFF
Speed man.
200 rpm
200 rpm
200 rpm
200 rpm
Events
3.04
2 sensors for dual circuit condensers
with input for refrigerant. Regulation
to the highest actual value Setpoint in
°
C .
Base setup
Mode
3.01
3.02
3.03
3.04
E1 Analog In
0-30 MBG0-30 MBG0-30 MBG0-30 MBG
E1 Refrigerant
R503
R503
E2 Function
E1 Min.
- - - -
- - - - -
- - - - -
- - - -
|
1E
|
external Setpoint
E1 Max.
- - - -
- - - - -
- - - - -
- - - -
E1 Decimals
- - - -
- - - - -
- - - - -
- - - -
|
2E
|
external manual mode
E1 Unit
- - - -
- - - - -
- - - - -
- - - -
E1 Offset
0.0 bar
0.0 K
0.0 bar
0.0 K
|
3E
|
Sensor average to E1
E2 Function
OFF
OFF
4E
4E
E2 Analog In
- - - -
- - - - -
0-30 MBG0-30 MBG
|
4E
|
Sensor comparison to E1
E2 Refrigerant
R503
E2 Min.
- - - -
- - - - -
- - - - -
- - - -
|
5E
|
Sensor difference to E1
E2 Max.
- - - -
- - - - -
- - - - -
- - - -
E2 Decimals
- - - -
- - - - -
- - - - -
- - - -
|
6E
|
Sensor for Setpoint
E2 Unit
- - - -
- - - - -
- - - - -
0.0 K
E2 Offset
- - - -
- - - - -
0.0 bar
0.0 K
|
7E
|
Measurement
Operating Instruction
Econtrol
–
model series EXDM
Programming
L-BAL-E008-GB 0945 Index 005
Part.-No. 00156742-GB
35/85