A1 Function
“
A min.
”
and
“
A max.
”
Analog
Out
5 V
10 V
0
50
100 0 -100 %
A max: 10 – 5V
A min: 0 – 5V
10.05.2007
v_a1_funktion_amin_amax.vsd
A1 Function
|
3A
|
/
|
4A
|
5 V
10 V
Analog IN
0
1
2
3
4
5
6
7
8
9
10
10
9
8
7
6
5
4
3
2
1
0
0
2
4
6
8
10
12
14
16
18
20
20
18
16
14
12
10
8
6
4
2
0
4
5,6
7,2
8,8
10,4
12
13,6 15,2 16,8 18,4
20
20
18,4 16,8 15,2 13,6
12
10,4
8,8
7,2
5,6
4
0 – 10 V
10 – 0 V
0 – 20 mA
20 – 0 mA
4 – 20 mA
20 – 4 mA
-27
-16.8
-6.6
3.6
13.8
24
34,2 44.4 54.6 64.8
+75
TF.. (KTY)
10.05.2007
v_a1_funktion_3a_4a.vsd
9.10.3
Digital inputs
“
D1
”
/
“
D2
”
9.10.3.1
Menu overview
D1 Function
The digital inputs Digital In 1 (D1) and Digital In 2 (D2) can be allocated with
various functions.
Activation via
oating contacts (a low voltage of approx. 24 V DC is con-
nected).
D1 Inverting
Inverting
“
D1
”
and
“
D2
”
possible
D1 Busmode
With networking the digital inputs can be replaced by control over bus.
With mode of operation
4.03
pre-setting of
“
D1
”
and
“
D2
”
is
|
ON
|
.
Attention!
Never apply line voltage to the digital input!
Function
Description
OFF
no function (factory setting)
1D
Enable (remote control)
“
ON
”
/
“
OFF
”
2D
External error
3D
“
Limit
”
ON / OFF
4D
Switch over
“
E1
”
/
“
E2
”
For mode speed controller
1.01
5D
Switch over
“
Setpoint Intern1
”
/
“
Setpoint Intern2
”
6D
Switch over
“
Intern
”
/
“
Extern
”
For modes as controller higher
2.01
5D
Switch over
“
Setpoint1
”
/
“
Setpoint2
”
6D
Switch over
“
Intern
”
/
“
Extern
”
7D
Switch over
“
automatic control
”
/
“
Speed manual
”
8D
Switch over control function (e.g.
“
heating
”
/
“
cooling
”
)
Operating Instruction
Econtrol
–
model series EXDM
Programming
L-BAL-E008-GB 0945 Index 005
Part.-No. 00156742-GB
54/85