9.12.5
Setting rated current
Attention!
When commissioning, you must set the motor to the rated current stated on the rating plate.
MotorRatedCurr.
MotorRatedCurr.
Setting range: 0.0...100.0 A
Factory setting: 6.0 A
E1 Actual
When the adjusted value is exceeded, the modulation is reduced as far as
necessary until it has readjusted itself.
Active current limit is signaled by a bright triangle in the display
9.12.6
Setting current display (only for controllers in sheet metal housing)
Econtrol > 10 A
Econtrol > 10 A
Only for controllers in sheet metal housing
with 10 A and 14 A switch
current display to
“
ON
”
.
9.12.7
Setting PI Mode
Over the hall sensors built in the motor the speed is measured and is supplied to the drive logic.
Dependent on the difference between measured actual speed and by the electronic given target
speed the modulation is affected.
Over the setting
“
PI Mode
”
the control mode can be adapted to the size of impeller. For heavy fan
impellers it can come with to fast rampup to overcurrent messages.
PI Mode
•
Setting 0: Operation without speed control, only for special applications
•
Setting 1:
factory setting
, for slow rampup of relativ heavy fan impellers.
•
Setting 2: for middle rampup (for lighter fan impellers).
•
Setting 3: for fast rampup (for light fan impellers).
9.12.8
Setting for Rampup time and Rampdown time
By separate menus for Rampup time and Rampdown time an adjustment is possible to individual
system conditions.
This function is switched behind the actual controller function.
Rampup time
Rampup time
Time setting in which the automatic controller output from 0 % to 100 % rises.
Setting range: 2...250 sec.
factory setting: 20 / 40 sec. (depending on device type)
Rampdown time
Rampdown time
Time setting in which the automatic controller output from 100 % to 0 %
reduces.
Setting range: 2...250 sec.
factory setting: 20 / 40 sec. (depending on device type)