E1 Actual
The activated heating is indicated over the
re symbol in the display.
Temperature variation with reprogramming to
|
10K
|
for
“
K2
”
in IO Setup, e.g., for activation of
the Cooling.
Example:
Setpoint 15.0
°
C, 5.0 K, Hysteresis 2.0 K
10
12
14
16
18
20
22
24
26
28
30
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
[min]
[°
C
]
ON
ON
ON
ON = 15°C + 5 K = 20 °C
OFF = 20°C - 2 K = 18 °C
16.
0
3
.2
0
07
v_
re
la
is
_ku
e
hl
en
_10
k
_p
os_
o
ff
se
t.
vs
d
If the ambient temperature is higher than the set
operating point, the cooling remains switched on. If
the ambient temperature falls below the set operat-
ing point of the cooling by 2 K (Kelvin), it is
switched off. I.e., the OFF point is situated at the
hysteresis value under the ON point.
9.2.6
For mode
2.03
Relay output for temperature monitoring
If the set value for the
“
minimum alarm
”
is not reached or the set value for the
“
maximum alarm
”
is
exceeded, a message is generated via the alarm symbol in the display. In addition,
„
Lmt E1 min
“
is
displayed alternately with the actual value for the minimum alarm and Lmt E1 max for the
„
Maximum
alarm
“
. An external message follows via the factory-assigned
“
K1 relay
”
. (IO Setup: K1 function =
|
2K
|
).
Alarm Minimum
Alarm Minimum
Setting range: OFF / -26.9...75.0
°
C
Factory setting: 0.0
°
C
Alarm Maximum
Alarm Maximum
Setting range: OFF / -26.9...75.0
°
C
Factory setting: 40.0
°
C
Lmt E1 min
Example for display if falling below setting
“
Alarm Minimum
”
alternating to the
actual value display.
Relay
“
K1
”
disengages (if not inverted).
Lmt E1 max.
Example for display if exceeding setting
“
Alarm Maximum
”
alternating to the
actual value display
Relay
“
K1
”
disengages (if not inverted).
9.2.7
Menu for Temperature controller
2.01
...
2.05
Parameter
Factory setting
User
Setting
Start
Motor
OFF
OFF
OFF
OFF
OFF
(Menu dependent on device type
available)
PIN input
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
Language
GB
GB
GB
GB
GB
Reset
OFF
OFF
OFF
OFF
OFF
Mode
2.01
2.02
2.03
2.04
2.05
Econtrol
1.14
1.14
1.14
1.14
1.14