10D
“
Reset
”
11D
Setting Max. Speed
“
ON
”
/
“
OFF
”
13D
Switch over direction of rotation
“
clockwise
”
/
“
counterclockwise
”
(only Fcontrol,
Icontrol)
14D
“
Freeze function
”
= maintain momentary modulation value
9.10.3.2
Enable ON/OFF function
|
1D
|
Remote ON/OFF (electronic disconnection) and Reset after a motor malfunction via
oating contact.
The power section is electronically disconnected. Operation of the device is still possible after
pressing the
“
ESC
”
hotkey combination in switched-off condition. Signal- in and outputs remain active.
•
A programmed operating indicator relay (factory set
“
K1 function
”
=
|
1K
|
) reports the switch-off.
•
A programmed alarm relay (factory set
“
K2 function
”
=
|
2 K
|
) does not report the switch-off.
Display STOP for switch OFF
•
Controller
“
ON
”
for closed contact
(factory setting).
•
Controller
“
OFF
”
with opened
contact
When inverting in reverse i.e. equip-
ment
“
OFF
”
with closed contact.
D1
D1
D1
D1
Digital IN 1
Digital IN 1
ON
OFF
10.05.2007
v_1d_freigabe_d1_d1.vsd
Contact at digital input e.g.
“
Digital In 1
”
Attention!
No disconnection (isolation) when turned off, in accordance with VBG4
§
6)!
9.10.3.3
External fault Function
|
2D
|
Connecting an external alarm indication (via
oating contact). The device continues to work un-
changed during an external indication to the digital input; the alarm symbol appears in the display.
This indication can be issued via the relay contacts (K1, K2) (
F
IO Setup function K1, K2).
•
Indication during closed contact (factory setting):
“
D1 Inverting
”
=
“
OFF
”
•
Indication during opened contact:
“
D1 Inverting
”
=
“
ON
”
Actual value
Alarm symbol for indication
“
External fault
”
Operating Instruction
Econtrol
–
model series EXDM
Programming
L-BAL-E008-GB 0945 Index 005