KD
D-component
More
“
D-component
”
causes more stability by a clean actual value signal with
shorter correction times
By a actual value signal with a superposition should be done to attitude
without
“
D-component
”
→
0 %
Setting range: 0 - 200 %
value smaller = less
“
D-component
”
value higher = more
“
D-component
”
TI
Integration time = correction time
Setting range: 0 - 200 %
smaller = faster
bigger = more slowly
9.9.11
Data on the total control deviation
The total control deviation is comprised of the sum of the control deviations for performance quantities
and work quantities combined and refers to the speci
ed areas.
In direct reference to the acquired input and controlled variables, the maximum deviation to the target
value is <
±
5 %. By activating the menu-assisted adjustment, the total control deviation can be
reduced to a value of <
±
1 %.
For indirect reference of the acquired input value to the controlled variable, i.e., two physical variables
still need to be converted, the deviation can be reduced to <
±
5 % through adjustment.
In the case of an internal default value through the integrated or external terminal, the control deviation
remains at <
±
0.5%.
9.10 IO Setup
9.10.1
Menu overview
“
IO Setup
”
IO Setup
IO Setup
Parameter
Factory setting
User Setting
A Function
1A (6A**)
A / A2 Function
A min.
0.0 V
|
1A
|
Constant v10 V
A max.
10.0 V
|
2A
|
proportional level control
A Inverting
OFF
|
3A
|
proportional input E1
A2* Function
1A
|
4A
|
proportional input E2
A2* min.
0.0 V
|
5A
|
Group control
A2* max.
10.0 V
|
6A
|
only 2.03 Cooling function
A2 Inverting
OFF
|
7A
|
only 2.03 Heating function
D1 Function
OFF
|
9A
|
proportionally to speed
D1 Inverting
- - - -
D1 Busmode
- - - -
D1...D5 function
D2 Function
OFF
|
1D
|
Enable ON / OFF
D2 Inverting
- - - -
|
2D
|
External error
D2 Busmode
- - - -
|
3D
|
Limit ON / OFF
D3* Function
OFF
|
4D
|
Switch over Signal E1/E2
D3* Inverting
- - - -
|
5D
|
Setpoint1/2
D4* Function
OFF
|
6D
|
Switch over: Intern/Extern
D4* Inverting
- - - - -
|
7D
|
Control / manual Intern
D5* Function
OFF
|
8D
|
Switch over: actual Val > Set = n+ / n-
D5* Inverting
- - - -
|
10D
|
Reset
E1 Inverting
OFF
|
11D
|
Setting Max. Speed ON / OFF
Operating Instruction
Econtrol
–
model series EXDM
Programming
L-BAL-E008-GB 0945 Index 005