13.1 STANDBY BATTERY REQUIREMENTS
It is the responsibility of the system designer to choose batteries that will give the required system standby time. The following
pages give the information needed to help determine the minimum battery requirements.
13.2 DEVICE CURRENT RATINGS
The Following Table shows the Quiescent, Alarm currents of the main parts of a Smart Connect Fire Alarm System:
DEVICE
QUIESCENT
ALARM
MKII-AOP
0.5
5
MKII-AOH
0.5
5
MKII-AHR
0.5
5
MKII-AHF
0.5
5
ZT-CP3/AD
0.45
2.3
ZT-CP3/AD/WP
0.45
2.3
MKII-AXT/x
0.65
4.5
MKII-AXTB/x
2.3
20.3
MKII-SSB
0.65
5.5
ZRAP/x
2.3
6.4
ZRAPB/x
2.3
20.3
ZAI-MI
1
3.6
ZAIO-MI
1
2
ZASC-MI
0.6
0.8
ZAZM-MI
3.5
13.2
ZAIOI/230
1.5
4.6
SMM/B
1.1
12
Wi-Fyre Transponder
12
12
MKII-CB
n/a
n/a
MKII-CB/D
n/a
n/a
MKII-IB
0.05
7
MKII-ARL/x
0.5
5
The Maximum per loop values given above are a guideline, based on the assumption that other devices on the loop do not cause
the total loop current to exceed the loop limit of 500mA.
Current readings may change in future updates.
*AXTB, ZRAP & ZRAPB Dip settings: 1000, current varies per switch settings.