10.1 WHY USE TEST MODE
To aid commissioning and assist routine maintenance check, a non-latching ‘one man test’ facility is available. Test mode can be
used either with or without sounder operation, depending on the engineer’s requirements.
When a detector, manual call point or input unit is triggered on any zone in Test, the Alarm sounders operate for approximately 10
seconds on and then switch off (If selected). The triggered device is automatically reset. The panel will display the tested device on
a test alarm screen, with the event highlighted in blue. The device automatically resets from the fire condition, but the LCD
indication remains until the panel is manually reset.
If the device is still in the fire condition, e.g. MCP still activated or the analogue value of a detector still above the alarm threshold,
the device will be triggered again and the Alarm sounders will operate for a further 10 seconds.
Should an Alarm occur on a zone that is not programmed to test, the Fire Alarm Panel will operate as normal.
10.2 TO PROGRAMME ZONE INTO TEST MODE
Enter the Engineer
or User Password
, Press the
menu access icon, and select the zone Icon
.
(The disabling function is available to engineer & users).
The panel shows the Zone menu
Select the zone(s) to be tested by clicking on the In Field, until it
shows Test
This will give a silent test, with no sounders operating.
If the sounders are required to operate, press the In Field again.
It will show Test + Sound.
This will operate all the sounders in that zone for approximately
10 seconds, regardless of the cause and effect programming
When all required zones have been selected, press exit and
accept the change. The panel will return to the menu, showing
that there is a Disablement or test condition present
.