8.2 OUTPUTS AND DELAYS
Following the indication of a fire, the panel will activate outputs (i.e. sounders and / or relays) according to the cause and effect
rules that have been programmed. In certain circumstances, the activation of outputs may be delayed whilst the fire is being
investigated.
8.2.1 Sounder Delays
If the operation of sounders has been delayed in one or more of the programmed ACTIONS, then this will be indicated by the
illumination of the DELAY ON LED (in the SOUNDER STATUS section of LEDs). When a fire has been indicated, the DELAY ON LED
remains lit until the longest sounder delay has expired.
During a fire alarm it is possible to override all the sounder delays (at any access level) by pressing the delay override icon
at
the bottom of the screen, as shown.
8.2.2 Relay Output Delays
Relay outputs can also be delayed via the cause and effect actions. In this case, no LED is lit to indicate a delay (since this type of
output is not mandatory).
8.2.3 Programming Delays
Delays to relays and/or sounders can be programmed as part of the cause and effect programming (See previous section). If the
delay will be permanently set, the delay should be entered into the NIGHT time delay field. If the delay is only to be set at certain
times of the day, the panel should be configured for day/night mode. See following section