7.6 ZONE LABELS
The reason for subdivision of a fire alarm system was explained earlier in the manual. The Smart Connect panel has 254 zones. The
first 16 zones also have LED indications. When a fire is reported, the zone number in which the fire is located is indicated on the
alphanumeric display. In addition to its numerical description, a zone can be identified by a text label, e.g. 3rd floor west ext. If the
installer associates a text label with each zone of a fire alarm system, this will be displayed on the LCD when a fire is detected. The
maximum length of the zone text label is 46 characters.
Enter the engineer password and select the zone Icon
Press on the zone text field. The panel displays it`s keyboard.
Use <- and -> to place the cursor, and to delete unwanted text.
Type the zone name, and press exit when done. Repeat for all
required zones.
The LCD also indicates the current mode of each zone – enabled, disabled or in test mode.
7.7 ADDRESS LABELS AND ZONING DEVICES
Smart Connect is an addressable panel, i.e. it will indicate the address or location of a fire that has been detected. The address
number of each point or device on the loop has already been set with the address programming tool. The installation engineer
must now assign a label or location for each device, e.g. ROOM 107. A maximum of 48 characters can be used for each label. At the
same time each point can be allocated to a zone.
From the ENGINEER MENU, press the Point Icon.
Press the text field of the device to be edited