Smart Connect
Single Loop Touch Screen Panel
Doc: GLT-229-7-1
74
Issue: 3
Date: 12/05/2017
11.7 CONFIGURING THE CLOUD SETTINGS
The Smart Connect panel has been designed to report events to a central server. This will allow authorised users to view the
current status of the panel. The settings are usually set at the factory, but can be configured by the installer if required.
From the Network Menu
, press the Cloud tab.
Enter Server and Port details as required. Make a note of the
MAC address, as this will be needed to register the panel at the
server.
The Mode setting determines whether remote access to the
panel is enabled or disabled.
To allow an engineer to interrogate the panel remotely, this
should be set to enabled. This is to prevent access to a panel
without a responsible person physically at the fire panel.
This setting will time out after a short period of inactivity.