VIEW GROUP 68
NO MORE POINTS
1=BACK,
<=EXIT
8. Press escape to exit the screen.
24.13How To Print The Allocation Of Devices To A Group
1. Enter the engineers menu as described in section 24.
2. Press 1 to select panel set-up. The following screen will be displayed:
1=LOOP SETUP
2=INPUT/OUTPUT SETUP
3=REPEATER SETUP
SELECT 1..2, <=EXIT
3. Press 1, 3, 1. The following screen will be displayed:
1=EDIT POINT GROUPS
2=PRINT POINT GROUPS
3=VIEW POINT GROUPS
SELECT 1..3, <=EXIT
4. Press 2 to print the point group allocation. If the printer is disabled press 1 to
override the disablement when prompted to do so. The report will be prepared:
PRINT POINT GROUPS
PREPARING REPORT
PLEASE WAIT
<=CANCEL
Press escape to cancel the report at any time.
5. While the report is printing the following message is displayed:
PRINTING
POINT GROUPS
<=CANCEL
Press escape to cancel the report at any time.
6. When the report is complete the following message is displayed:
PRINTING
POINT GROUPS
COMPLETE
<=EXIT
7. Press escape to exit the screen.
Page 91 of 111
02/10/03